Fluke 1777 - Electrical Power Quality Analyzer

Sku: 297276
Fluke
The strong points
  • Automatic measurement of power and electrical network quality parameters

  • Intuitive user interface

  • High-speed voltage transient capture

€11,473.00 €13,767.60
- +
On order

The Fluke 1770 series three-phase power quality analyzers help solve the complexities associated with recording, troubleshooting, and analyzing power quality. Designed as a faster and simpler method for conducting power quality studies, the 1770 series offers automatic measurements, an intuitive user interface and setup, premium features, and a simplified report creation platform. Additionally, the instrument can be powered directly from the measurement circuit: no need to find a power outlet or use a long extension cord.
With the 1770 series, you won't miss any events critical to power quality: from fast transients up to 8 kV to harmonics up to 30 kHz, including sags and swells, as well as voltage, current, and power measurements that allow you to characterize your electrical system.

Comes with:

- 4 iFlex1500 current probes

- Three-phase + N voltage measurement cord

- 4 black AC285 alligator clips

- 4 green AC285 alligator clips

- 1m black USB-C cable

- Power cord

- Set of 0.18m measurement cords, non-stackable

- Green measurement cord

- Magnetic sensor, 3 red magnetic sensors/1 black for 4mm banana plug

- Suspension kit

- Wi-Fi/BLE module

- Cable markers set (for voltage and current)

- MA-C8 wall plug adapter

- Best practices calibration guide

- Fluke-1777 hard case

Courant max AC (A) 6000 A
Courant max DC (A) 2000 A
Tension max 1000 V
Caractéristiques techniques
- Number of inputs: 4 inputs, three-phase and neutral referenced to the PE conductor (5 connectors)
- Measurement category: 1,000 V CAT III/600 V CAT IV
- Maximum input voltage: 1,000 V rms / 1,000 V DC (1,700 Vpk)
- Input impedance: 10 MΩ between PP and PN, 5 MΩ between PPE and NPE
- Bandwidth: DC to 30 kHz for electrical network quality measurements, except transients
- Sampling frequency: 80 KS/s at 50/60 Hz